Supply Requirements
230V±10%, 45-65Hz 1ph 11.5kVA max (23kVA overload for 2s)
Control Unit Standard Accessories Supplied
Mains lead (5m), loading unit power and metering leads (5m), operating
manual and spare fuses.
Dimensions
PCU1-SP/PCU1-LT 450(W) x 275(H) x 305mm(D)
NLU2000/NLU5000 450(W) x 275(H) x 370mm(D) incl. terminals
Weight
PCU1-LT 29kg, PCU1-SP 35kg.
Temperature Range
Storage -20°C to 60°C, Operating 0°C to 45°C
Protection and Safety
The PCU1 series and loading units are CE marked and are designed to meet
the requirements of BS EN61010. The system is protected by electronic
trips on the outputs, circuit breakers on the mains input, control unit
output and secondary injection output (PCU1-SP only). The unit also has a
duty cycle trip on the loading unit output and the loading unit has
comprehensive thermal protection.
Optional Loading Unit Specifications
Two loading units are available to provide a range of output currents
suitable for different primary injection tasks. Each loading unit has
three output taps allowing current injection into a wide range of loads of
differing impedances. Optional output lead sets are also available. |