Powertech Rentals your One Stop Store for Test & Measurement and Telecommunication Test Equipment Rental and Sales

 
Relay Test Sets >  DVS3 Mk2 > Specifications

Relay Test Sets

 
T&R Test Equipment DVS3 Mk2 Relay Test System
 
Product Description

The DVS3 mk2 is smaller, lighter, higher power version of the T&R DVS3, offering more than twice the output power of the original DVS3.

Equally at home in a commissioning, maintenance, or laboratory environment, the DVS3 mk2 is a truly flexible system. The DVS3 Mk2 has been designed using the latest digital technology to generate a highly stable and accurate output with very low distortion. Each phase output is individually adjustable for voltage and phase angle. In addition, full control of frequency is available. Step changes of any quantity may be generated with automatic timing of the response of the relay under test.
 

T&R Test Equipment DVS3 Mk2 Relay Test System Features
  • 3-Φ Voltage output from 1-Φ supply.
  • 0 to 133V Φ-N output voltage, 0 to 266V or 0 to 292V Φ-N with optional VT box.
  • 45VA/phase maximum output.
  • Variable Frequency 40 to 999.9Hz.
  • Phase shift ±180°.
  • Multi-functional timing system.
  • Ideally suited to testing G59 schemes.
  • Step change of phase and df/dt.
  • Large back-lit liquid crystal display.
  • Compact and lightweight.
  • Automatic mains voltage selectable.

DVS3 Mk2 Specifications
 

The display on the DVS3 is back-lit and exceptionally clear. Menu options on the left are selected by dedicated buttons on the panel next to the display, allowing immediate access to adjust voltage, phase and frequency.

The unit is controlled by a simple user interface with context sensitive menus. Values may be either typed in at the keypad or smoothly varied using a digital potentiometer.

The display on the DVS3 is back-lit and exceptionally clear. Menu options on the left are selected by dedicated buttons on the panel next to the display, allowing immediate access to adjust voltage, phase and frequency. Phase to phase and phase to neutral voltages are both shown on the display, along with frequency and phase information. A graphical vector diagram is shown, as is the state of the two contact inputs.


The DVS3 mk2 is ideally suited to testing G59 protection, including loss of mains protection. Vector surge and df/dt (ROCOF) relays may be simply tested and timed, as can other protection requiring one to three voltages, including:

  • Under and over relays.

  • Under and over voltage relays.

  • Synchronizing relays.

  • df/dt and ROCOF relays.

  • Vector surge relays.

  • Transducers.

In conjunction with a current source (such as the 200ADM or 50A-3PH) the DVS3 mk2 can be used to test protection requiring current injection with a phase-shiftable voltage including:

  • Directional relays.

  • Distance protection.

  • Phase angle relays.

  • Power relays.

  • Power transducers.

50A-3PH/ DVS3 mk2 Combined Data Sheet (PDF)
(documents are in PDF format and will open in a new window)


DVS3 mk2 Modes of Operation

Variable Frequency Mode
This mode allows full control of frequency, voltage and phase. The voltage and phase may be controlled individually for each phase or for all three phases together. All parameters are continuously variable using the adjust control, and step changes of any value may be generated by typing the required value on the keypad. The new value is applied to the output when the enter key is pressed. The timer automatically resets and starts when a step change of value is entered, and stops if either contact input changes state. Step changes of phase for testing Vector Surge relays are easily generated in this mode.

Frequency Resolution
 

0.01Hz
0.1Hz

40.00 to 99.99Hz
100.0 to 999.9Hz

Frequency Accuracy

±0.01% of reading +1 digit

 

Phase Resolution

0.1°

 

Phase Accuracy

±0.3° phase to phase

 

Phase Lock Mode
The frequency and phase of the output are controlled by an external reference in phase lock mode. The reference may be the mains supply to the DVS3 MK2, an external voltage, or an external current. This mode allows testing of directional and distance protection in conjunction with an external current source.

Phase Lock Range

45 to 65Hz

External Voltage Ref.

20V AC to 250V AC

External Current Ref.

0.2 to 5A AC

Phase Resolution

0.1°

Phase Accuracy
 

±0.3° phase to phase
±0.3° reference to output

df/dt and ROCOF (Rate Of Change Of Frequency)

Frequency Range

45.00 Hz to 65.00Hz

Default Sweep Range

49.75 to 50.25Hz (50Hz supply)
59.75 to 60.25Hz (60Hz supply)

Rate of Change Range

0.010 to 2.000Hz/s

Pre-fault - Fault - Post-fault Mode
PF-F-PF mode allows extra flexibility in testing where complex events must be timed or several sets of values must be applied to a relay in turn. This mode allows three sets of values to be set in advance (pre-fault, fault, and post-fault values). The DVS3 mk2 may be set to switch from one state to the next on a change of contact or after a specific time. In addition, the timer may be set to start or stop on any one of the state changes of a change of contact state. This mode allows frequency, phase and voltage to be changed simultaneously if required.

 
Rental Inquiry Information
 

Reference:

DVS3 Mk2

Description:

T&R Test Equipment DVS3 Mk2 Relay Test System
 


Home | About Us | Product Category | Test & Communication | Mechanical Tools | Safety Items | Feedback | Search |
Test and Measurement Site Map | Telecommunications Site Map

8 Hasler Road

Powertech Rentals Pty Ltd

  70 Fison Avenue West
Osborne Park, WA 6017

A.B.N. 85 082 324 918

  Eagle Farm, Qld 4009
Ph: 61 8 9244 2855

1300 736 292

  Ph: 61 7 3268 1378
Fax:61 8 9244 4478

sales@powertech-rentals.com.au

  Fax: 61 7 3268 1374