| Technical Specifications |
| |
| Seaward 300 PAT Tester |
| |
| Earth Continuity |
| Test Current |
±200mA DC |
| Display Range |
0.01 ohm to 19.99 ohms |
| Pass Value |
User defined |
|
| |
| |
| Insulation Resistance |
| Test Voltage |
500 volts DC @ 1mA nominal |
| Display Range |
0.01 Megohm to 40 Megohms |
| Pass Value |
User defined |
|
| |
| |
| IEC Lead Test |
| Tests Performed |
Earth continuity |
| Insulation resistance |
| Live/Neutral checks for o/c, s/c and crossed |
|
| |
| |
| Protective Conductor Current |
| Test Voltage |
230 volts |
| Display Range |
0.0mA to 19.99mA |
| Pass Value |
User defined |
|
| |
| |
| Touch Current |
| Test Voltage |
±200mA DC |
| Display Range |
0.0mA to 3.50mA |
| Pass Value |
User defined |
|
| |
| |
| RCD Trip Time |
| Test Current |
30mA rms |
| Test Current Phase |
0°/180°
auto switched |
| Display Range |
0ms to 200ms |
|
| |
| |
| Earth Loop Resistance |
| Test Current |
Non-tripping for >30mA RCD |
| Display Range |
0.0 ohm to 199 ohms |
|
| |
| |
| Power Socket Test |
| Input Voltage Range |
230V +10%, -15% AC |
| Indicators |
Phase to Earth Voltage |
| Phase to Neutral Voltage |
| Neutral to Earth |
|
| |
| |
| General Specifications |
| Dimensions |
260mm x 100mm x 55mm |
| Weight |
950g |
| Power Source |
6 x 'AA' NiMH rechargeable batteries |
|