Measurement Functions
Measurements on earthing and lighting protection systems include:
- Standard 4-wire method.
- Standard 4-wire method with current clamps.
- 2-clamp method without junctions disassembling.
Specific earth resistance (soil resistance) measurement with:
- 4-wire method up to 30 meters deep.
- True RMS current measurement.
|
Earth Resistance Measurement
- 2-pole, 3-pole, 4-pole earth resistance measurements.
- Selective earth resistance measurement with clamp (no
influence from parallel earths).
- Two clamp earth measurement for quick testing in urban areas.
Specific Earth Resistance (Φ)
Measurement
- True RMS current measurement for determining problems on earth
systems and conductors.
- Outstanding features even in presence of mains interference
and high probe resistance.
- Warnings indication for out of limits results and incorrect
test conditions.
- 1000 memory locations and PC Software for print-out of
measurement protocol.
- Socket for external battery charger.
- Auto power-off.
|
Measurements and Testing in
Accordance With:
EN/IEC 61557-5; DIN/VDE 0100
BS7671; 16th Edition; CEI; EN/IEC 61010-1Typical
Connection
 |
|
| Technical Specifications |
|
|
| Earth Resistance (four-lead method) |
|
Display Range |
0 - 19.99kΩ |
|
Resolution |
0.01, 0.1, 1, 10Ω |
|
Basic Accuracy |
±(2% + 3
digits) , (0 - 2kΩ |
|
Test Voltage |
<40V/125Hz/sine wave |
|
Short-circuit Test Current |
<20mA |
|
High Noise Rejection |
Yes |
|
Aut. Potential and Current Probe
Resistance Test |
Yes
|
|
| |
| |
| Earth Resistance (four-lead method + clamp) A1018 |
|
Display Range |
0 - 1.99kΩ |
|
Resolution |
0.01, 0.1, 1, 10Ω |
|
Basic Accuracy |
±(2% + 3
digits) , (0 - 2kΩ |
|
Test Voltage |
<40V/125Hz/sine wave |
|
Short-circuit Test Current |
<20mA |
|
High Noise Rejection |
Yes |
|
Aut. Potential and Current Probe
Resistance Test |
Yes
|
|
| |
| |
| Earth Resistance (two test clamps) A1018, A1019 |
|
Display Range |
0 - 19.99Ω, 20.0 -
100.0Ω |
|
Display Accuracy |
±(10% + 2
digits) , ±(20%) |
|
| |
| |
| Specific Earth Resistance |
|
Display Range |
0 - 1999kΩ per
meter , (kΩ ft) |
|
Calculation |
p=2∏aRE |
|
Distance between Test Rods |
1 to 30 meters (1 - 90ft) |
|
| |
| |
| Current (True-RMS) (Clamps A1018, A1019) |
|
Measurement Principal |
current clamp 1A/1mA |
|
Display Range |
0 - 200A |
|
Resolution |
0.1, 1mA, 0.01, 0.1, 1A |
|
Basic Accuracy |
±(5% + 5
digits) , (0.5mA - 200A) |
|
Nominal Frequency |
50/60Hz |
|
| |
| Rental Inquiry Information |
| |
|
Reference: |
MI2124 |
|
Description: |
Metrel MI2124 Earth Tester |
|
| |