Powertech Rentals your One Stop Store for Test & Measurement and Telecommunication Test Equipment Rental and Sales

 
Current Injection > GE SVERKER 760

Current Injection

   
GE Sverker 760 Current Injection Set 1ph - 200A  c/w Phase Shift
 

The Sverker 760 Relay Test Unit is the engineers toolbox. The Sverker 760 features many functions that make relay testing more efficient, for example, it's powerful measurement section can display (in addition to time, voltage and current) Z, R, X, S, P, Q, phase and cos.

The voltmeter can be used as a second ammeter. You can also test directional protective equipment efficiently by means of the built-in variable voltage source. The Sverker 760 also has a continuous phase shift function. The 760 is designed to comply with EU Standards and other personal and operational safety standards, Sverker 750 is also equipped with a Serial Port for communication to a PC. (PC software required)
 

GE Sverker 760 Current Injection Set 1ph - 200A  c/w Phase Shift

 



Sverker 760 Specifications (PDF)
(documents are in PDF format and will open in a new window)
 

 

Applications
  • The model 760 is intended primarily for secondary testing of protective relay equipment. Virtually all types of single-phase protection can be tested.
  • The 760 is able to test three-phase protection that can be tested one phase at a time, and also a number of protective relay systems that require phase shifting. Moreover, automatic reclosing devices can be tested.
  • Plotting excitation curves.
  • Current and voltage transformer ratio tests.
  • Burden measurement for protective relay test equipment.
  • Impedance measurement.
  • Injection Maintained:
    Injection continues without any time limitation.
  • Injection Momentary:
    Inject continues only as long as the button is kept depressed.
  • Maximum Time:
    Injection stops automatically when the preset maximum time is reached.
  • Filtering:
    When filtering is selected, five successive readings are averaged.
  • Off Delay:
    The turning off of generation can be delayed after tripping throughout a specified time interval that is expressed in mains-frequency cycles.
Specifications
AC Current Outputs

Range
 

No-load Voltage
(minimum)
Full-load Voltage
(minimum)
Full-load Current
(maximum)
Load/Unload Times
On (max) Off (min)

0 - 10A

90V

75V

10A

2/15 minutes

0 - 40A

25V

20V

40A

1/15 minutes

0 - 100A

10V

8V

100A

1/15 minutes

0 - 100A

10V

-

250A

1 sec/5 minutes

The output transformer is equipped with built-in temperature protection. The primary side is protected by a miniature circuit breaker.
   
   
AC/DC Outputs

Range
 

No-load Voltage
(minimum)
Full-load Voltage
(minimum)
Full-load Current
(maximum)
Load/Unload Times
On (max) Off (min)

0 - 250V AC

290V

250V

3A

10 min/45 min

0 - 300V DC

320V

250V

2A

10 min/45 min

   
 
Rental Inquiry Information
 

Reference:

760

Description:

GE Sverker 760 Current Injection Set 1ph - 200A c/w Phase Shift
 


Home | About Us | Product Category | Test & Communication | Mechanical Tools | Safety Items | Feedback | Search |
Test and Measurement Site Map | Telecommunications Site Map

8 Hasler Road

Powertech Rentals Pty Ltd

  70 Fison Avenue West
Osborne Park, WA 6017

A.B.N. 85 082 324 918

  Eagle Farm, Qld 4009
Ph: 61 8 9244 2855

1300 736 292

  Ph: 61 7 3268 1378
Fax:61 8 9244 4478

sales@powertech-rentals.com.au

  Fax: 61 7 3268 1374