CPC 100
Multifunctional Primary Test System for Substation Commissioning and Maintenance
OMICRON's world-wide unique primary test system CPC 100 allows for automated testing of power transformers, current transformers (CTs) and voltage transformers (VTs), and resistance testing. The patented device comes complete with an integrated PC, allowing stand-alone operation. Its software routines test a wide range of substation equipment, and automatically create customizable reports. The CPC 100's compact design and the innovative software save testing time and minimize transportation costs.
Features and Benefits
- Wide range: up to 800 A (or 2000 A with current booster) and 2000 V with a frequency range of 15-400 Hz
- High precision measuring of analog voltages and currents
- Ohm meters offer ranges from µOhm to kOhm to allow a wide variety of applications
- Portable, lightweight and easy to handle: less than one fourth of the weight of equivalent conventional equipment (29 kg / 64 lbs)
- One device for multiple application replaces need for multiple test sets and saves training costs
- User-friendly interface
- Automated testing: test plans can be prepared ahead of time in office – this saves time in field testing phase
- Automatic report generation
- Prepared for the future: Tests even of unconventional equipment like Rogowski Coils or current sensors
- Unit accessible in a network or with direct PC connection via standard internet protocols
Applications
Current Transformer (CT) Testing
- Ratio, burden and polarity
- Phase and magnitude error
- Excitation curve
- Winding resistance
- Secondary burden
- Dielectric withstand voltage (2 kV AC)
- CT circuit continuity
Voltage Transformer (VT) Testing
- Ratio and polarity
- Phase and magnitude error
- Secondary burden
- Dielectric withstand voltage (2 kV AC)
- VT circuit continuity
Power Transformer Testing
- Ratio
- Winding resistance
- Tap change testing
- Excitation current
- Short circuit impedance
- Leakage reactance
Resistance
- Contact resistance
- Winding resistance
- Ground resistance
- Measuring of complex impedances
Additional Information
The CPC 100 Basic Unit can be extended in various ways: By adding the CP TD1 it becomes a flexible insulation diagnosis system.
In combination with the CP CU1 coupling unit the CPC 100 becomes a safe and most accurate system for measuring primary power system parameters, such as line and ground impedances, k-Factor and mutual coupling.
* $784.00 a day approx. Call for a firm price