| Test Voltage/Range |
500V |
| |
1000V |
| |
2500V |
| |
5000V |
|
| 30kΩ to 2000GΩ (2TΩ) |
| 100kΩ to 4000GΩ (4TΩ) |
| 100kΩ to 10,000GΩ (10TΩ) |
| 300kΩ to 10,000GΩ (10TΩ) |
|
User Selectable Test Voltage
|
| Programmable: |
|
40 to 1000V
|
10V Increments
|
|
1000V to 5100V
|
100V Increments
|
|
| Accuracy |
1kΩ to 40GΩ |
| |
40GΩ to 10TΩ |
|
| ±5% of Reading ±3cts |
| ±15% of Reading ±10cts |
|
Voltage Test/Safety Check
|
0 to 1000V AC/DC (16 to 420Hz)
1V Resolution
|
| Voltage Warning Indicator |
Yes >25V
|
Test Inhibition(1)
|
Yes - adjustable from 25 to 1000V
depending on test voltage range
in use
|
Smooth Function (user selectable)
|
Digital filtering stabilizes display readings
|
| Storage of Readings over Time R(t) |
128KB memory |
| Report Print Out Direct to Printer |
Preset format |
| Storage of Test Results |
Stores over 1500 test results |
| Communication Port |
RS-232 |
| PC Application Software/Report Generation |
Yes (included) |
| Power Source |
Eight NiMH rechargeable batteries
Line power: 85 to 256V (50/60Hz) |