GE Sverker 750 Current Injection Set 1ph - 200A

The Sverker 750 Relay Test Unit is the engineers toolbox. The Sverker 750 features many functions that make relay testing more efficient, for example, it's powerful measurement section can display (in addition to time, voltage and current) Z, R, X, S, P, Q, phase and cos.

The voltmeter can be used as a second ammeter. Designed to comply with EU Standards and other personal and operational safety standards, Sverker 750 is also equipped with a Serial Port for communication to a PC. (PC software required)

GE_Sverker_750_760.jpg

Applications

  • The model 760 is intended primarily for secondary testing of protective relay equipment. Virtually all types of single-phase protection can be tested.
  • The 760 is able to test three-phase protection that can be tested one phase at a time, and also a number of protective relay systems that require phase shifting. Moreover, automatic reclosing devices can be tested.
  • Plotting excitation curves.
  • Current and voltage transformer ratio tests.
  • Burden measurement for protective relay test equipment.
  • Impedance measurement.
  • Injection Maintained:
    Injection continues without any time limitation.
  • Injection Momentary:
    Inject continues only as long as the button is kept depressed.
  • Maximum Time:
    Injection stops automatically when the preset maximum time is reached.
  • Filtering:
    When filtering is selected, five successive readings are averaged.
  • Off Delay:
    The turning off of generation can be delayed after tripping throughout a specified time interval that is expressed in mains-frequency cycles.

Sverker 750 Specifications (PDF)
(documents are in PDF format and will open in a new window)

Specifications
AC Current Outputs

Range No-load Voltage
(minimum)
Full-load Voltage
(minimum)
Full-load Current
(maximum)
Load/Unload Times
On(max) Off(min)
0 - 10A 90V 75V 10A 2/15 minutes
0 - 40A 25V 20V 40A 1/15 minutes
0 - 100A 10V 8V 100A 1/15 minutes
0 - 100A 10V - 250A 1 sec/5 minutes

The output transformer is equipped with built-in temperature protection. The primary side is protected by a miniature circuit breaker.

AC Voltage Outputs

Range No-load Voltage
(minimum)
Full-load Voltage
(minimum)
Full-load Current
(maximum)
0 - 60V AC 70V 60V 0.25A
0 - 120V AC 130V 120V 0.25A

Both ranges are divided into voltage steps of 10V that are steplessly variable.

Rental Inquiry Information

Reference: 750
Description: GE Sverker 750 Current Injection Set 1ph - 200A

*$234.00 a day approx, Call for a firm price